Re: Communication problems between IX and Siemens S7-1500
HELLO, I also met the problem it is already necessary to put in ix Developer the slot to 1 in the parameters of communication. Then in TIA Portal it is necessary to go to the cpu and to the properties / protection and checked the box all below to authorize the exchanges towards a HMI. ScreenHunter_1...