Hi All,
The right mouse button is often used to open contextual menus, which are pop-up menus that change depending where you click.
I removed "Clear"button from Alarm Viewer screen, but...
for "advanced" HMI operators I need to remove "Clear" from Context Menu. How to do it?
Thanks,
Ilgonis
Context menu in Alarm Viewer
Context menu in Alarm Viewer
- Attachments
-
- ScreenShot004.png (44.19 KiB) Viewed 13910 times
iX Developer 2.20 SP1 / iX Box Pro C2D
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
-
- Posts: 824
- Joined: Tue Mar 13, 2012 9:53 am
Re: Context menu in Alarm Viewer
You can only enable or disable the context menu. There is currently no way to edit it.
Best Regards,
Mark Monroe
Beijer Electronics, Inc. | Applications Engineer
Mark Monroe
Beijer Electronics, Inc. | Applications Engineer
Re: Context menu in Alarm Viewer
Hi Mark,
Thanks for the answer!
In this case, maybe there is a way to assign Security Group Restrictions for "Clear" button?
Thanks for the answer!
In this case, maybe there is a way to assign Security Group Restrictions for "Clear" button?
- Attachments
-
- ScreenShot010_1.png (8.87 KiB) Viewed 13896 times
iX Developer 2.20 SP1 / iX Box Pro C2D
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
-
- Posts: 824
- Joined: Tue Mar 13, 2012 9:53 am
Re: Context menu in Alarm Viewer
Unfortunately you can not set security groups on buttons in the Alarm Viewer.
Best Regards,
Mark Monroe
Beijer Electronics, Inc. | Applications Engineer
Mark Monroe
Beijer Electronics, Inc. | Applications Engineer
Re: Context menu in Alarm Viewer
Here is my version of security groups on buttons in the Alarm Viewer.
Of course it is stupid and probably wrong way, but if Beijer Electronics support does not offer a better solution...
I recorded this in a video and can be viewed with Webex tool (freely downloadable from the internet).
Below i attached video file (Clear_1) and player setup file (atrecply).
Regards,
Ilgonis
Of course it is stupid and probably wrong way, but if Beijer Electronics support does not offer a better solution...
I recorded this in a video and can be viewed with Webex tool (freely downloadable from the internet).
Below i attached video file (Clear_1) and player setup file (atrecply).
Regards,
Ilgonis
- Attachments
-
- atrecply.7z
- (3.25 MiB) Downloaded 687 times
-
- Clear_1.7z
- (518.72 KiB) Downloaded 855 times
iX Developer 2.20 SP1 / iX Box Pro C2D
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
Re: Context menu in Alarm Viewer
Ok,
Here is simple way to solve problem:
1) create tag to clear alarms (in Alarm Server Settings tab); 2) uncheck from respective boxes (in Alarm Wiewer General tab); 3) create button called 'Clear";
4) set security for this button in Tag/Security; Done.
Only one question ( in next post).
Regards,
Ilgonis
Here is simple way to solve problem:
1) create tag to clear alarms (in Alarm Server Settings tab); 2) uncheck from respective boxes (in Alarm Wiewer General tab); 3) create button called 'Clear";
4) set security for this button in Tag/Security; Done.
Only one question ( in next post).
Regards,
Ilgonis
iX Developer 2.20 SP1 / iX Box Pro C2D
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
Re: Context menu in Alarm Viewer
Only one question: how to make button 1:1 as in Alarm Viewer.
In picture attached below:
Button1 made from Buttons selection (simply, but impossible to repeat as in Alarm viewer),
Button2 (1:1 as in Alarm Viewer) made from combination of rectangle & text (all ok, but button is complicated). Regards,
Ilgonis
In picture attached below:
Button1 made from Buttons selection (simply, but impossible to repeat as in Alarm viewer),
Button2 (1:1 as in Alarm Viewer) made from combination of rectangle & text (all ok, but button is complicated). Regards,
Ilgonis
iX Developer 2.20 SP1 / iX Box Pro C2D
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP
PME 9.0 / IC695CPE305
GE TCP/IP via SRTP